JZX4Cross-Type Quad-Bundle Spacer Damper

The JZX4 cross-type spacer damper is designed for quad-bundle conductors on high-voltage and extra-high-voltage overhead transmission lines. Its four-arm aluminum-alloy structure maintains the specified spacing between subconductors while integrated damping elements help control aeolian vibration and subspan oscillation. Conductor-clamp diameter, bundle spacing, mechanical performance and hardware configuration can be customized according to the approved line design.

JZX4 Cross-Type Quad-Bundle Spacer Damper

The JZX4 cross-type quad-bundle spacer damper is installed between four subconductors in an overhead transmission-line bundle. Its principal functions are to maintain the designed bundle geometry, prevent excessive subconductor movement and help reduce wind-induced vibration and subspan oscillation.

The product consists of a cross-shaped central frame, four articulated arms, conductor clamps, fastening hardware and damping elements. The four conductor clamps are positioned at equal intervals around the central frame to support a quad-bundle conductor arrangement.

The frame and clamp bodies are generally manufactured from high-strength aluminum alloy to provide a suitable combination of mechanical strength, low weight and corrosion resistance. Elastomer damping components may be incorporated into the articulated joints to dissipate vibration energy while permitting controlled movement of the conductor bundle.

Important: The spacer damper must be selected according to the actual conductor outside diameter, bundle spacing, short-circuit forces, vibration conditions, installation position and approved transmission-line design. A visually similar model must not be substituted without dimensional and mechanical verification.

Key Features

  • Cross-shaped configuration for four-subconductor bundles
  • Maintains the designed spacing between bundled conductors
  • Helps reduce aeolian vibration and subspan oscillation
  • Articulated arms allow controlled conductor movement
  • Aluminum-alloy frame and conductor-clamp construction
  • Elastomer damping elements available according to model
  • Rounded conductor grooves help avoid localized conductor damage
  • Bolted clamp design supports installation and inspection
  • Suitable for high-voltage and extra-high-voltage overhead lines
  • Conductor diameter, bundle spacing and clamp configuration can be customized

Typical Technical Specifications

Product Series JZX4 Series
Product Type Cross-Type Spacer Damper
Bundle Configuration Quad Bundle / Four Subconductors
Frame Configuration Cross-Shaped / X-Shaped
Main Function Subconductor spacing and vibration control
Frame Material Aluminum alloy, subject to approved material specification
Clamp Body Material Aluminum alloy
Damping Element Elastomer or project-specific damping material
Fasteners Galvanized steel or stainless steel, depending on specification
Clamp Type Bolted articulated conductor clamp
Representative Bundle Spacing 450 mm; other spacing available according to line design
Representative Conductor Diameter Approximately 23–30 mm, subject to the selected model
Installation Installed between four bundled subconductors
Application High-voltage and extra-high-voltage overhead transmission lines
Reference Standard IEC 61854:2020
Customization Conductor diameter, bundle spacing, clamp groove, damping element, marking and packaging

The dimensions and conductor range shown above are representative selection references only. Final values must be confirmed using the approved product drawing and conductor data.

Structure and Components

Cross-Shaped Central Frame

The central aluminum-alloy frame maintains the geometric relationship between the four arms and transfers mechanical forces throughout the assembly. Its shape is designed to provide adequate rigidity while controlling the total weight of the fitting.

Articulated Spacer Arms

Four articulated arms connect the central frame to the conductor clamps. The joint structure permits limited relative movement while maintaining the specified spacing between the four subconductors.

Conductor Clamps

Each arm terminates in a conductor clamp matched to the specified conductor outside diameter. The clamp groove, liner arrangement and tightening requirements must be compatible with the conductor construction.

Damping Elements

Elastomer components may be installed within the articulated joints to absorb and dissipate vibration energy. Their material formulation, hardness and environmental resistance must be selected according to the required operating conditions.

Operating Principle

Wind acting on a bundled conductor can produce aeolian vibration and relative movement between subconductors. The spacer damper maintains the required bundle geometry while its articulated arms and damping elements absorb part of the movement and dissipate mechanical energy.

The resulting performance depends on the conductor type, span length, bundle spacing, spacer-damper placement, wind environment and complete line design. The product should therefore be evaluated as part of the complete conductor motion-control system.

Applications

  • Four-bundle overhead transmission conductors
  • High-voltage transmission lines
  • Extra-high-voltage transmission lines
  • Long-span overhead conductor systems
  • Transmission lines exposed to aeolian vibration
  • New line construction and conductor-bundle refurbishment

Product Selection

The following information is required when selecting a JZX4 spacer damper:

  • Conductor type and designation
  • Conductor outside diameter
  • Number of subconductors in the bundle
  • Required bundle spacing
  • Transmission-line voltage class
  • Span length and spacer-damper installation positions
  • Expected wind and vibration conditions
  • Required mechanical load and short-circuit performance
  • Applicable standard and utility specification

Installation Guidance

  1. Confirm that the model matches the conductor diameter and bundle spacing.
  2. Inspect the frame, arms, clamps and damping elements before installation.
  3. Position the spacer damper at the location specified in the approved stringing chart.
  4. Place each subconductor correctly inside its corresponding clamp groove.
  5. Ensure that the conductor surface is not trapped against a sharp edge.
  6. Tighten all fasteners evenly to the specified installation torque.
  7. Check the orientation and geometry of the completed four-conductor bundle.
  8. Verify that all locking devices have been correctly installed.

Installation must be carried out by qualified line personnel using the approved installation instructions and torque values for the exact product model.

Quality Inspection

  • Raw-material and alloy-composition inspection
  • Dimensional and conductor-groove inspection
  • Visual inspection for casting defects, cracks and sharp edges
  • Fastener and locking-device inspection
  • Clamp-slip and mechanical-load testing when specified
  • Articulation and damping-performance verification
  • Corrosion-resistance inspection of steel components
  • Vibration and fatigue testing according to the agreed test program
  • Marking, packaging and quantity inspection

Reference Standard

  • IEC 61854:2020 – Overhead lines – Requirements and tests for spacers
  • Applicable utility drawings and transmission-line project specifications
  • Approved conductor and spacer-damper installation schedules

IEC 61854 covers rigid spacers, flexible spacers and spacer dampers used with bundled conductors. Mentioning this standard is for product-selection reference and does not constitute certification. Compliance must be supported by test reports for the exact model supplied.

Ordering Information

Please provide the following details when requesting a quotation:

  • JZX4 model or approved product drawing
  • Conductor designation and outside diameter
  • Required bundle spacing
  • Clamp-groove and liner requirements
  • Required mechanical and damping performance
  • Fastener material and corrosion-protection requirements
  • Applicable standard and required test reports
  • Required quantity, marking and packaging

Frequently Asked Questions

Is the JZX4 spacer damper suitable for twin-bundle conductors?

No. The cross-shaped JZX4 configuration shown is intended for four-subconductor bundles. Twin-bundle conductors require a compatible two-conductor spacer or spacer damper.

Can it be selected only according to the voltage level?

No. Voltage class alone is insufficient. Conductor diameter, bundle spacing, mechanical loads, vibration conditions and the approved line design must also be considered.

Does it completely eliminate conductor vibration?

No spacer damper can guarantee the complete elimination of all conductor movement. It is designed to help control vibration and maintain bundle geometry as part of an engineered motion-control system.

Can the same clamp be used for different conductor diameters?

Only when the approved clamp-groove range covers those conductor diameters. An incorrect groove can cause conductor slip, excessive pressure or surface damage.

Can IEC compliance be displayed on the product page?

IEC 61854 may be listed as a reference standard. A formal compliance claim should be made only when the exact supplied model has the corresponding test documentation.

Model

JZX4 Series

Product Type

Cross-Type Spacer Damper

Bundle Configuration

Quad Bundle, Four Subconductors

Frame Type

Cross-Shaped, X-Shaped

Frame Material

Aluminum Alloy

Clamp Material

Aluminum Alloy

Damping Element

Elastomer, Rubber

Clamp Type

Bolted Articulated Clamp

Reference Bundle Spacing

450 mm

Reference Conductor Diameter

23–30 mm

Function

Subconductor Spacing, Vibration Damping

Application

HV Transmission Line, EHV Transmission Line

Reference Standard

IEC 61854:2020

Customization

Conductor Diameter, Bundle Spacing, Clamp Groove, Damping Element, Marking

Brand

JIUJIN POWER