35kV Three-Core Outdoor Heat Shrink Cable Termination Kit
The 35kV three-core outdoor heat shrink cable termination kit is designed for the outdoor termination of screened three-core polymeric-insulated medium-voltage power cables. It provides electrical stress control, phase insulation, environmental sealing and an extended surface creepage path at the cable termination point.
The kit is suitable for connecting three-core power cables to outdoor switchgear, transformers, cable termination structures and other medium-voltage electrical equipment. Each phase is protected by an anti-tracking heat shrink tube and multiple rain sheds, while the cable crutch area is sealed with an adhesive-coated breakout component.
Reference Configuration
| Product Type | Three-Core Outdoor Heat Shrink Cable Termination Kit |
|---|---|
| Reference Model | 35kVRSWY-3/3 |
| Voltage Class | 35kV class |
| Reference Rated Voltage | 26/35kV |
| Number of Cable Cores | 3 cores |
| Reference Conductor Range | 150–240 mm² |
| Compatible Cable Insulation | XLPE or other screened polymeric insulation, subject to cable dimensions |
| Conductor Material | Copper or aluminium |
| Installation Environment | Outdoor |
| Reference Installed Length | Approximately 1100 mm |
| Reference Dimension D | Approximately 140 mm |
| Rain Sheds | 18 pieces total for the three-phase assembly |
| Terminal Lugs | Optional; selected separately according to conductor material and equipment interface |
Important: The dimensions and conductor range above describe a representative configuration. Final selection must be based on the actual diameter over cable insulation, conductor cross-section, metallic screen, armour construction and terminal interface.
Key Features
- Designed for outdoor termination of screened three-core medium-voltage power cables
- Electrical stress-control tube and stress-relief mastic help control the electric field at the screen cut
- Anti-tracking heat shrink phase tubes provide phase insulation and surface protection
- Multiple rain sheds extend the creepage path for outdoor service
- Adhesive-coated breakout seals and protects the three-core cable crutch area
- Heat-activated sealing components help limit moisture entry at critical interfaces
- Suitable for copper or aluminium conductors when fitted with the corresponding terminal lugs
- Different kits are available for conductor size, insulation diameter, cable screen and armour construction
Materials and Construction
| Anti-Tracking Tubes and Rain Sheds | Heat-shrinkable anti-tracking polymer |
|---|---|
| Electrical Stress-Control Components | Stress-control tube and stress-relief mastic |
| Cable Breakout | Adhesive-coated heat-shrink breakout component |
| Environmental Sealing | Heat-activated sealing tubes and sealing mastic |
| Earthing Components | Selected according to the cable metallic screen and armour construction |
| Terminal Lug | Tinned copper or copper-aluminium lug according to conductor and equipment requirements; normally ordered separately |
| Surface Protection | Weather-resistant and anti-tracking heat-shrink insulation; metal lug finish is specified separately |
Applications
- 35kV outdoor power cable termination
- Medium-voltage distribution networks
- Outdoor transformer cable connections
- Substation cable termination structures
- Outdoor switchgear and electrical equipment connections
- Industrial power distribution systems
- Wind and solar power collection systems
- Utility and infrastructure cable projects
Cable Selection Information Required
To select the correct termination kit, please provide the following cable information with your inquiry:
- Rated cable voltage
- Number of cable cores
- Conductor material and cross-sectional area
- Diameter over conductor insulation
- XLPE or other insulation material
- Copper wire screen, copper tape screen or other screen construction
- Armoured or unarmoured cable construction
- Required terminal lug type and palm-hole dimensions
- Applicable project standard and test-document requirements
Standards and Testing
For 26/35kV cable systems with a maximum system voltage above 36kV, IEC 60840 is the relevant IEC reference for cables and accessories. Compliance must only be stated when the supplied product is supported by the corresponding type-test report or project-approved documentation.
IEC 60502-4 applies to cable accessories only up to 18/30(36)kV and should not automatically be claimed for a 26/35kV termination kit.
Ordering Information
Please confirm the cable datasheet or provide the cable model, rated voltage, conductor size, insulation diameter, screen construction and armour type before ordering. Terminal lugs, earthing components and installation accessories can be configured according to the approved cable and equipment drawings.
Frequently Asked Questions
Is this termination suitable for 26/35kV XLPE cable?
It can be configured for screened 26/35kV three-core XLPE power cable. Final compatibility depends on the cable insulation diameter, screen design, armour construction and conductor size.
Can the kit be selected only by conductor cross-section?
No. Conductor cross-section is a preliminary reference. The diameter over insulation and the complete cable construction must also be checked before confirming the kit.
Are cable lugs included?
Terminal lugs are normally selected separately because copper and aluminium conductors require different lug materials and equipment interfaces. Please confirm the required lug type when requesting a quotation.
Why are rain sheds used on the outdoor termination?
The rain sheds increase the surface creepage path and support outdoor insulation performance under rain, dust and other environmental exposure.
Can the kit be supplied for armoured cable?
Yes, but the armour type and earthing arrangement must be confirmed so that the appropriate sealing and grounding components can be supplied.